Skip to content

About

**To use this repo, please clone and add the Library repository to matlab path.** Analysis and investigation on SST.

Topics

Resources

Stars

8 stars

Watchers

0 watching

Forks

Latest commit

 

History

102 Commits

Folders and files

Repository files navigation

solid-state-transformers

Simulink/Simscape study of solid-state transformer (SST) architectures built from modules, where a module is a galvanically isolated DC-DC converter followed by a single-phase inverter: modules are paralleled on the DC side and their inverters are series-connected on the AC side. The repository holds the two-module SST bench (two CLLC DC transformers of the library feeding two three-level T-type single-phase inverters in series on the line), the bench of the isolated stage alone as a CLLC DC transformer (DCX, 800 V / 800 V, 50 kW, 50 kHz, SiC, with a 35 kHz variant at 790 V / 700 V) and first-cut sizing scripts for the medium-frequency transformers. The single-phase DAB variant of the SST bench was removed on 2026-10-24 (still in the git history).

Earlier variants with two-level and NPC inverters and with a three-phase DAB were removed from the tree in March 2026 (still in the git history); the three-phase DAB study lives in advanced-dcdc-converters. Simulation results are discussed in the solid_state_transformers document published on the organization page (pwr-control/docs/solid_state_transformers).

Prerequisites

  • MATLAB with Simulink, Simscape and Simscape Electrical.
  • The companion library repository on the MATLAB path with subfolders (every init_model.m of this repository does it by itself through its private/library_setup.m, cloning the library next to this repository when it is missing): the CLLC-DCX block cllc_dcx/cllc_dcx_mod1 (Simscape-language power stage cllc_ssc, to be built once with ssc_build cllc_ssc from library/foundation/pwr_electronics), masked power stages (three-level T-type inverter with thermal model, three-level PWM modulator with global TRGO, DC link, lithium-ion battery, single-phase transformer, mos_simple_2th), the dq_vector_pi control block, and the setup classes and functions used by init_model.m (init_environment, timing_setup, hw_single_phase_inverter_setup, ctrl_single_phase_inverter_setup, hw_cllc_single_phase_setup, ctrl_cllc_setup, device_mosfet_setup, lithium_ion_battery_setup, cllc_dcx_param_example, ...).

How to use a project

  1. Run init_model.m in the project folder: it builds the param structure (one group per subsystem: param.sim, .time, .glb_time, .cllc, .spinv, .grid, .battery, .thermal, ...; the numbers of the bench are in private/*_param.m, those of the DCX in cllc_dcx_param_example.m of the library), prints the operating point and opens the model. The SST bench runs 1.25 s with the inverters at 4 kHz (double update) and the DCX at 50 kHz, 2 × 50 kW, two 800 V packs, wolfspeed_SiC_MOSFET_CAB006M12GM3 with thermal model (its init_model.m holds the simulation settings only, the rest is built in private/); the CLLC-DCX benches run 0.25 s with the last 50 ms logged. All of them use the Simscape Backward Euler local solver with the fixed step param.sim.tc (1 µs in the SST bench, 50 to 500 ns in the DCX benches: the method damps the resonant tank in proportion to tc, see the READMEs).
  2. Simulate the .slx. In the SST bench, the first time, run update_sst_cllc_ttype_inv.m before simulating (it fixes the model around the library DCX blocks and saves it).
  3. Post-process with power_loss_calculus.m, plotting_results.m and spectrum.m; figures go to figures/ (EPS, ignored by git).

Each converter runs on its own local time base (time_master, time_afe_module_A/B, time_cllc_module_A/B in the SST model, the local clock of the DCX block): the modulators generate the control triggers, and the local clocks can be detuned to study the effect of time sliding between modules.

Repository layout

Folder Content
theory_analysis_solid_state_transformer The two-module SST bench (CLLC-DCX + T-type inverters), the CLLC-DCX benches of the isolated stage (800 V / 800 V at 50 kHz, and a 35 kHz variant at 790 V / 700 V) and the transformer sizing scripts

The folder has its own README with the project descriptions.

About

**To use this repo, please clone and add the Library repository to matlab path.** Analysis and investigation on SST.

Topics

Resources

Stars

8 stars

Watchers

0 watching

Forks

Releases

Packages

Used by

Contributors

Languages